|
for about a peak voltage swing of 140 volts, not the 430 volts that I·R = voltage dictates. Remember that wattage increases by the square of the voltage, so twice the voltage, means four times the watts. But with only 140 volts to play with, the maximum output wattage would be in reality only 2 watts or so. Here is the math:
140 / 4300 = 32.5 mA [(32.5 ma)² x 4300] / 2 = 2.27 watts
Quite a bit less than 50 watts. The situation can be improved by the suggestion made in the article, namely by mis-tapping the output transformer. This topic always upsets neophytes. You see a transformer really does not have a set impedance. Instead, it has a winding ratio. The winding ratio sets the voltage and current reduction or expansion of the transformer. Squaring the winding ratio will yield the impedance ratio of the transformer. For example, if a transformer has a winding ratio of 10:1, then 100 volts delivered into the primary will result in 10 volts at the secondary; 1 ampere into the primary results in 10 amperes at the secondary. Notice that the product of current and voltage on both sides of the transformer equal each other: 100 x 1 = 10 x 10. The transformer transfers power, it does not create it. If a 1 ohm resistor is attached to the secondary, then its resistance will multiplied by the winding ratio squared at the primary: 1 ohm x 10² = 100 ohms. Notice again that the transfer of power worked out to unity: 10 volts divided by 1 ohm equals 10 amps and 10 volts times 10 amps equals 100 watts; 100 volts divided by 10 ohm equals 1 amps and 100 volts times 1 amps equals 100 watts. Nothing gained, nothing lost. (In actual practice, expect a loss of 5 to 10 percent, as no transformer is perfect.) Now if the transformer is specified at 4300 ohms when working into an 8 ohm load, then the winding ratio must be Ö(4300 / 8) = 23.2:1. Therefore, if we replace the 8 ohm load with a 4 ohm load, reflected impedance at the primary will be 2150 ohms; a 16 ohm load, 8600 ohms. Or we can connect the 8 ohm load to the wrong tap, say the nominally 16 ohm one, which would give us the same 2150 ohms of the 4 ohm load hooked up to the 8 ohm tap. Now let us redo the math:
140 volts / 2150 ohms = 65 mA, (65mA x 140 volts) / 2 = 4.5 watts RMS
Here is a quiz: what would be the optimal load impedance for the most watts in this amplifier, given the 100 mA idle current and 140 voltage swing limit?
// editor
|
|